Note: All references are to the RLED 2 Manual.
Problem Description | Troubleshooting |
The power is connected, yet the LEDs are off. |
1. Check the power. 2. Check the main fuse F3. 3. Using a DVM, test the +5 and COM test points (refer to Figure 12). 4. Check flat cable connection. |
Power is ON, but there is no Output when working in "AUTO" mode with "0-10V" control voltage. | Make sure the "+" and "COM" of "0-10V" cable is connected correctly. Set 5V from the controller and measure this value at the RLED 2.0 terminal. |
Power is ON, but there is no Output when working in "AUTO" mode with communication lines. |
1. Check the dipswitches and ensure that they are set correctly (refer to Figure 8 and Figure 9, page 16). 2. Check the wiring. |
The lights blink when working at low voltage levels. |
1. Make sure there is no inductive devices (for example transformers and power coils) integrated into the electrical load system. 2. In Options > Cn, change the Cn setting. This step requires recalibration. Refer to System Parameter 1 – Minimum Light Calibration (bu), page 9) 3. Apply Ignition Pulse. |
Light is always at maximum brightness or you can't change the brightness. | Contact technical support. |